TM 55-1925-273-10-2
0117 00
AFFF Monitor
1
Pilothouse Top
Figure 3. Fire Monitor
START THE PUMP
1.
At the machinery DC control distribution panel, set the PMP DR ENG circuit breaker (figure 4, item 1) to ON.
1
Figure 4. Machinery DC Control Distribution Panel
2.
To start the pump drive engine:
a.
Place the Power Take-Off (PTO) control lever (figure 5, item 1) in the disengaged (aft) position.
b.
Move the governor control lever (figure 6, item 1) to the half engine speed position (approximately straight up).
c.
Check the PMP DR ENG STG AIR PRESS gauge. The starting air pressure must be 100 PSI (6.9 bar) to operate
properly.
d.
OPEN CA-6, STG AIR TO PMP DR ENG (figure 1, item 15).
e.
Turn the EMERGENCY/STOP pushbutton (figure 6, item 2) clockwise to release the pushbutton to the OUT
position.
0117 00-4


 