Custom Search
 
  
 
TM 55-1905-219-14-2
2-43. STOPPING GENERATOR OPERATING - PARALLEL.
a.
The following procedure applies to either generator 1 or 2 operating in parallel.
b.
This procedure will transfer the load to generator #1, and shutdown generator #2. The procedure for shutting
down generator #1 is the REVERSE of the following procedure.
(1)
Transfer the load to generator #1 as follows:
(a)
Do both parts of this step simultaneously. Rotate the generator #1 governor motor switch (1) to RAISE.
Rotate the generator #2 governor motor switch (2) to LOWER.
(b)
Observe generator #2 wattmeter (3) and ammeter (4). As the governor motor switches (1 and 2) are rotated,
the meter readings will decrease.
(c)
When the readings on generator #2 wattmeter (3) and ammeter (4) are zero - proceed as follows:
(2)
Place the generator #2 main circuit breaker (5) in the OFF position.
(3)
Place the unit parallel switches (6 and 7) in the ON position.
(4)
Rotate the generator #2 voltage adjust rheostat (8) to the DECREASE position.
(5)
Proceed with local shut down of the generator as per paragraph 2-44.
2-288


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business