Generator Engine - Abnormal Engine Operation Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Uneven running or frequent stalling (Cont).
Step 3.
Check for faulty injectors.
a.
Check the injector timing and the position of the injector racks. Refer to paragraph
3-87.
b.
Erratic engine operation may also be caused by leaking injector spray tips. Replace
the faulty injectors.
Refer to paragraph 3-71.
Step 4.
Check for low compression pressures within the cylinders.
Consult the Hard Starting Table 3-23 if compression pressures are low.
3-85


 