Custom Search
 
  
 
TM 55-1905-223-10
c. On Fire Pump Motor Switch (FIGURE 2-239), press STOP (2) and slide LOCK (3) upwards to lock-in
STOP pushbutton (2) for both fire pumps.
d. Close FM-11, FOAM STA 2 and PORT MONITOR ISLN (14, FIGURE 2-238).
e. Close FM-12, FOAM STA 1 and STBD MONITOR ISLN (13).
f. Close FM-10, FIREMAIN ISLN (6).
g. Close FM-15, NO. 2 FIRE PUMP DISCH (15).
h. Close FM-14, NO. 1 FIRE PUMP DISCH (16).
i. Close FM-17, FIRE PUMP NO. 2 SUCT (18).
j. Close FM-18, FM-18, FIRE PUMP NO. 1 SUCT (21).
k. Close FM-26, NO. 2 FIRE PUMP STRAINER ISOLATION (19).
l. Close FM-25, NO. 1 FIRE PUMP STRAINER ISOLATION (20).
CAUTION
Before proceeding, ensure the BILGE/BALLAST PUMP and Watermaker have
been shutdown or damage to this equipment could result.
FIGURE 2-239. Fire Pump Motor Switch.
2-634


 


Privacy Statement - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business