TM 55-1905-219-14-8
4-5. GENERAL (Continued).
Table 4-7. Air Conditioner Erratic Operation
Troubleshooting.
NOTE
Refer to paragraphs 4-28 and 4-29 for air conditioning and compressor
maintenance instructions.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Compressor will not start.
Step 1.
Power off.
Check main switch and fuses. Throw in switch or replace blown fuses.
Step 2.
Loose electrical connections or faulty wiring.
Tighten connections. Check wiring and rewire, if necessary.
Step 3.
Dirty control switch contacts.
Clean contacts on all control switches.
Step 4.
Low voltage, relay tripped.
Reset relay. Correct cause of low voltage.
Step 5.
High pressure control switch contacts opened.
Find and eliminate cause of high pressure cut-out before restarting. (If provided, press
reset button on dual pressurestat.)
Step 6.
Oil safety switch tripped.
Find and eliminate cause of low oil pressure.
If provided, press oil switch reset
button.)
Step 7.
Solenoid thermostat set too high.
Reset.
4-34
|
||