TM 55-1905-219-14-8
4-5. GENERAL (Continued).
Table 4-9. Air Conditioner System Noises Troubleshooting (Continued).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step 2.
Loose pipe connections.
Check pipe connections. Tighten as required.
3. Hissing.
Step 1.
Insufficient refrigerant flow through thermal expansion valves.
Adjust expansion valves and check refrigerant charge. Add refrigerant, if required.
Step 2.
Clogged liquid line strainer.
Pump down, remove and clean strainer.
4-42