4-5. GENERAL (Continued).
Table 4-10. Air Conditioner Capacity Control
Troubles Troubleshooting.
NOTE
Refer to paragraphs 4-28 and 4-29 for air conditioning and compressor
maintenance instructions.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. Compressor will not unload.
Step 1.
Capacity control valve inoperative.
Repair or replace.
Step 2.
External adjusting stem damage.
Remove stem housing and inspect. Replace if necessary.
2. Compressor will not load.
Step 1.
Low oil pressure.
Check oil pressure with capacity control valve adjusting stem turned all the way out.
Oil pressure should be 45 - 55 psi above crankcase pressure.
Step 2.
Capacity control valve stuck open.
If control oil pressure is low for all adjustment stem positions, repair or replace control
valve.
Step 3.
Control valve adjusting stem traveling nut out of guide or stem broken.
Remove stem housing and inspect. Engage nut or replace stem.
Step 4.
Control oil strainer blocked.
If control oil pressure cannot be raised by adjusting control valve, clean or replace
strainer.