4-5. GENERAL (Continued).
Table 4-21. Hot Water Heater Troubleshooting.
NOTE
Refer to paragraph 4-65 for maintenance instructions.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
No hot water.
Step 1.
Check circuit breaker #6 on power distribution panel (P-401).
Tighten loose wires.
Reset circuit breaker.
Step 2.
Low line voltage.
Check incoming power.
Step 3.
Move thermostat dial up and down. A definite "snap" should occur.
Replace thermostat.
2.
Water temperature below setting at all times.
Step 1.
Check thermostat adjustment.
Readjust if necessary.
Step 2.
Check that element is working on all phases. Clamp amprobe individually
around each of the three wires and compare readings. If reading is not the
same on all wires check for blown fuse.
If fuses are O.K. then element must be replaced.
4-80


 