TM 55-1905-220-14-1
Table 2-1. PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) - continued
Item
Location Item to
Not Mission
No
Interval
Check/Service
Procedure
Capable If :
126
MONTHLY
Air Conditioning
AIR CONDITIONING COOLING
Strainer
Room
PIPING STRAINER. Shut valve
plugged.
(8). Loosen strainer cap. Then
remove bolts (10), holddown (9) and
strainer cap (11). Remove strainer
basket (12). Clean strainer basket
(12) and shell (13). Replace strainer
basket (12), strainer cap (11) and
bolts (10). Tighten strainer holddown
(9). Open valve (8).
SCREEN. Close valve (8). Remove
Strainer
cap (14) and attach hose. Close
plugged.
valve (15). Open valve (16). Turn on
water. The screen will be reversed
flushed.
Turn off water. Close valve (16).
Open valve (15) and (8). Remove
hose and close cap (14).
Change 5
2-182