TM 55-1905-220-14-2
2-43. STOPPING GENERATOR OPERATING - NON PARALLEL.
The following procedures applies to either generator #1 or generator #2 operating by itself (non-parallel).
a. Reduce the load as mush as possible by placing circuit breakers on the power distribution panels in the OFF
position.
b. Place the generator main circuit breaker (1 or 2) in the OFF position.
c. Place auto/manual switch in the manual position. Turn the voltage regulator rheostat (3 or 4) to decrease.
d. Shut down the generator as per paragraph 2-44.
2-400
Change 2


 