TM 55-1905-220-14-2
2-44.
STOPPING GENERATOR OPERATING - PARALLEL.
a. The following procedure applies to either generator 1 or 2 operating in parallel.
b. This procedure will transfer the load to generator #1, and shutdown generator #2. The procedure for shutting
down generator #1 is the REVERSE of the following procedure.
(1) Transfer the load to generator #1 as follows:
(a) Do both parts of this step simultaneously. Rotate the generator #1 governor motor switch (1) to RAISE.
Rotate the generator #2 governor motor switch (2) to LOWER.
(b) Observe generator #2 wattmeter (3) and ammeter (4). As the governor motor switches (1 and 2) are
rotated, the meter readings will decrease.
(c) When either meter drops below 5 amps or watts, open #2 generator main circuit breaker and proceed as
follows:
(2) Place the generator #2 main circuit breaker (5) in the OFF position.
(3) Place the unit parallel switches (6 and 7) in the ON position.
(4) Place auto/manual switch in the manual position. Rotate the generator #2 voltage adjust rheostat (8) to the
DECREASE position.
(5) Proceed with local shut down of the generator as per paragraph 2-45.