TM 55-1905-220-14-3
Table 3-22.
Generator Engine - Exhaust Analysis Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
5.
White smoke.
Check for faulty injectors and replace as necessary.
Refer to paragraph 3-71.
Check for low compression.
Consult the Hard Starting Table 3-23.
Table 3-23.
Generator Engine - Hard Starting - Troubleshooting.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Engine will not rotate.
Step 1.
Check hydrostarter.
Refer to tables 3-11 through 3-21, and perform the operations listed.
Step 2.
Check for defective starting motor switch in either the engine access room or
engine room.
Replace the starting motor switch in the engine room. Refer to paragraph 3-99.
Refer to Direct Support Maintenance for the switch in the engine access room.
Step 3.
Check for internal seizure.
Crank the engine at least one complete revolution. If the engine cannot be rotated
a complete revolution, internal damage is indicated and the engine must be
disassembled to ascertain the extent of damage and the cause. Refer to paragraph
3-64.
3-80


 