Table 3-43.
Switchboard Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
9.
Shore power not available (Cont).
Step 3.
Check for shore power not turned on at source.
Turn power on.
10.
Shore power available - but not to load.
Step 1.
Check shore power circuit breaker.
Reset circuit breaker.
Step 2.
Check distribution circuit breaker.
Reset circuit breaker.
Step 3.
Check defective circuit breaker.
Refer to Direct Support Maintenance.
11.
Step 1.
Check for defective governor on generator.
Replace. Refer to paragraph 3-66.
12.
Generators do not parallel properly.
Step 1.
Check for defective governor on engine.
Refer to paragraph 3-66.
Step 2.
Check for improper adjustment.
Perform operating procedure.