Custom Search
 
  
 
TM 55-1905-220-14-3
Table 3-43.
Switchboard Troubleshooting (Cont).
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
13.
Ground detector lights.
AO
BO
CO
Normal
Glow
Phase A Ground
Bright
Phase B Ground
Bright
Phase C Ground
Bright
If light is dark and others are not brightly lit, the light bulb or lamp holder may be
loose or defective. Refer to paragraph 3-59.
Table 3-44.
24VDC Rectifier Troubleshooting.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
WARNING
DEATH or SEVERE INJURY can occur if personnel fail to observe safety pre-
cautions. Be sure the circuit breaker to the battery charger is in the OFF position.
Tag the circuit breaker to prevent accidental turn on.
1.
Batteries not charged.
Step 1.
Check circuit breaker on power distribution panel.
Reset.
3-133


 