TM 55-1905-223-10
NOTE
Generator/diesel engines, except main engines, on the LCU have an Automatic
Low Oil Pressure Shutdown System. This system will activate at a low oil pressure
condition and shut engine down.
NOTE
If engine speed is not between 600 and 650 rpm, notify unit maintenance.
j.
Set IDLE-RUN switch (5) to RUN position.
k.
Set EXCITATION SWITCH (6) to ON position.
l.
On Main Switchboard (FIGURE 2-95), set AUTO OFF MANUAL switch (3) to AUTO position.
m. On Main Switchboard (FIGURE 2-95), turn GENERATOR 1 SPEED CONTROL (4) to read 60 Hertz
on the GENERATOR 1 FREQUENCY METER (6).
n.
On Main Switchboard (FIGURE 2-95), set VOLTMETER SWITCH (10) to phase of generator No. 1.
o.
Adjust GENERATOR 1 VOLTAGE ADJUST RHEOSTAT (7) to read 240 volts on GENERATOR 1
VOLTMETER (5).
p.
Adjust GENERATORi1 SPEED CONTROL (4) to read 60 Hertz on GENERATOR 1 FREQUENCY
METER (6).
NOTE
If generator is started with AUTO OFF MANUAL switch (3) in MANUAL position,
voltage adjustment is made by EXCITATION CONTROL (9).
q.
On Main Switchboard (FIGURE 2-95), set GENERATOR 1 CIRCUIT BREAKER as follows:
(1) Turn CIRCUIT BREAKER LOADING ARM (11) 90 degrees.
(2) Return CIRCUIT BREAKER LOADING ARM (11) to the vertical position.
(3) On Main Switchboard (FIGURE 2-95), set SHORE POWER SWITCH <17) to NORMAL
position.
(4) On Main Switchboard (FIGURE 2-95), push CLOSE pushbutton (12) to release circuit breaker
spring and place GENERATOR 1 on line.
(5) On Emergency Switchboard (FIGURE 2-96), set MAIN SWBD BUS TIE circuit breaker (1) to ON
position.',
(6) On Main Switchboard (FIGURE'2-95), set circuit breakers (13, 14, and 15) to ON position.
Change 1