Custom Search
 
  
 
TM 55-1905-223-10
WARNING
The FM-200 system has been outfitted with a time delay override
located on top of the time delay.
When the time delay override lever is pulled, the 60 second time
delay is negated and FM-200 will immediately discharge into the
protected spaces.
This procedure should only be performed under extreme
circumstances and with the authority of the watch officer or scene
commander.
Failure to observe these warnings could result in serious injury
or death.
Operate the WWS for a minimum of fifteen (15) minutes. During the WWS operating
period, approximately every three (3) minutes, open valve WWS-2, Bow Thruster Room
WWS Strainer Blow Off for approximately ten (10) seconds. This will allow any foreign
matter to be flushed from the strainer basket.
WARNING
To reduce temperatures within the protected space and manage
the risk of HF exposure to humans, the WWS is designed and
intended to be operated for a minimum of 15 minutes. This
procedure should be followed to the full extent or death or serious
injury could occur.
NOTE
The bow thruster room FM-200 system is augmented with an
installed WWS. If necessary, the FM-200 system could be used
as a stand alone system.
e. Actuation Procedures, Paint Locker FM-200 System. All fire scenarios and situations
leading to the decision when to actuate the FM-200 total flooding fire extinguishing system
are not intended to be discussed here. Refer to the US Army Fire Fighting Doctrine for
guidance. However, the following steps must be completed to effectively deploy the FM-200
system as designed.
In the event the FM-200 Fixed Fire Fighting System is to be actuated, the following steps must
be accomplished prior to activation of the system.
WARNING
To reduce temperatures within the protected space and manage
the risk of HF exposure to humans, the WWS is designed and
intended to be operated for a minimum of 15 minutes. This pro-
cedure should be followed to the full extent or death or serious
injury could occur.
(1) Evacuate all personnel from space. The Watch Officer or on-scene commander must
ensure all personnel have evacuated the space and are accounted for.
Change 10