TM 55-1905-223-10
(2) Secure Ventilation. Secure powered ventilation to the protected space. This can be
accomplished locally at the motor-controller if the situation allows during the evacuation
process, at the FM-200 storage cylinder located in the bow thruster room by manually
lifting the plunger located on top of the FM-200 pressure switch, or by shutdowns that
occur automatically during FM-200 system actuation.
Ensure the following powered ventilation systems are secured:
Paint Locker Supply Fan SF-3
Secure the following openings to the protected space:
OPENING
LOCATION
Paint Locker Natural Supply Cover
Main Deck Weather Area (1-0-0-WEA), Port
Side, Frame 5
Paint Locker Powered Exhaust Vent
Main Deck Weather Area (1-0-0-WEA), Port
Cover
Side, Frame 12
Paint Locker Watertight Door
Main Deck, Port Side, Watertight Bulkhead 13
REMEMBER An actual fire emergency is not the time to train
to perform these procedures!
NOTE
The responsibilities to perform these space preparations listed
above have been identified on the LCU-2K station bill for fire and
damage control conditions and crew members should routinely
train for these responsibilities.
(3) Break Glass On FM-200 Pull Station. Initiate actuating the FM-200 fixed fire fighting
system for the paint locker by breaking the glass for access to the pull handle.
The pull station is found in the following area:
NOTE
Actual location may vary slightly between vessels.
Paint locker pull station located on the exterior of the paint locker aft bulkhead, main
deck weather area (1-0-0-WEA), watertight bulkhead 13. This exterior watertight pull
station requires first opening the watertight cover to expose the glass.
(4) Pull Lever On FM-200 Pull Station. Actuate the FM-200 system by pulling the handle. The
lever requires less than 40 pounds force and 6 inches of pull to operate. Allow no one to
enter the protected space until authorized to do so.
WARNING
The paint locker FM-200 system is not fitted with a time delay.
Upon actuation of FM-200 system, siren will sound for approximately
10 seconds and FM-200 will be discharged immediately. The warning
bell will sound until manually reset.
In the event the FM-200 system siren or warning bell is activated,
always leave the protected space immediately. FM-200 is being
released, death or serious injury could occur.