TM 55-1905-223-24-18-1
Repair Analog Remote Module Assembly.
This task covers:
a. Disassembly, b. Repair, c. Assembly.
INITIAL SETUP
Tools
Equipment Condition
T o o l kit, electrician's,
Electrical power to machinery plant
monitoring and alarm system secured
and tagged "Out of Service - Do Not
Materials/Parts
Operate" at ship service switchboard.
(TM 55-1905-223-10).
Fuses P/N 68-00G09-001
Warning tag, Item 1, Appendix
a.
Unscrew two captive screws (1) securing door (2).
Swing door to the left to
open.
Remove fuse (3) from fuse holder in printed circuit board B1.
b.
c.
Remove fuse (4) from fuse holder in printed circuit board B2.
d.
Remove fuse (5) from fuse holder in printed circuit board B3.
Repair at this level of maintenance is by replacement of fuses (3).
Make sure replacement fuses are of the same size and rating as
ones removed.
ASSEMBLY
a.
Install fuse (5) in fuse holder of printed circuit board B3.
Install fuse (4) in fuse holder of printed circuit board B2.
b.
Install fuse (3) in fuse holder of printed circuit board B1.
c.
Close door (2) and secure with two captive screws (1).
d.
2-528
Change 1