Custom Search
 
  
 
TM 55-1905-223-24-18-1
(1) Position fuseholder blocks (8 and 9) over mounting screw holes on motor
controller panel.
(2) Install machine screws (14), lockwashers (13) and plain hex nuts (12) and
secure terminal block to motor controller panel.
Remove tags.
(3) Connect electrical leads to fuseholder blocks.
( 4 ) Install fuse cartridges (10 and 11).
Transformer.
g.
(1) Position transformer (4) over mounting screw holes on motor controller
panel.
(2) Install four machine screws (7), lockwashers (6) and plain hex nuts (5)
and secure each terminal block to motor controller panel.
Remove tags.
(3) Connect electrical leads to transformer.
Auxiliary contact.
h.
(1) Position motor starter (19) on a clean flat surface.
( 2 ) Attach auxiliary contact (23) to motor starter (19).
(3) Secure auxiliary contact with two attaching screws (22) to motor starter.
(4) Connect electrical leads to auxiliary contact.
(5) Repeat steps (2) through (4) to install auxiliary contact on opposite side
of motor starter, if applicable.
Thermal release relay.
i.
(1) Position thermal release relay (20) on motor starter with control circuit
wire exposed.
Remove tag.
(2) Connect control circuit wire to thermal release relay.
(3) Secure thermal release relay to motor starter base plate with three
machine screws (21).
Electrical contact assembly.
j.
(1) Compress and install push bar springs into spring slots on each armature
lever relay push bar.
(2) Install armature lever relay push bars into magnet housing as noted during
disassembly.
(3) Position electrical contact assembly (25) on armature lever relay push
bars at rear of magnet housing.
2-805


 