TM 55-1905-242-14
OPERATOR MAINTENANCE
FOR LANDING CRAFT, MECHANIZED (LCM-8) (ALL VESSELS WITH MOD 2 APPLICATION)
OPERATOR TROUBLESHOOTING PROCEDURES
220/110 VAC ELECTRICAL SYSTEM
INITIAL SETUP:
Personnel Required:
References:
One Watercraft Engineer, 88L
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1. Air conditioner raw water
1.
Check that the circuit breaker for the pump is
Set to ON the circuit breaker.
pump is inoperative.
ON (refer to WP 0019 00)
2.
Check that at least one heating/cooling unit
Turn ON at least one heating/
is ON.
cooling unit.
2. Shore power does not
1.
Ensure that the shore power supply is
Energize the shore power
power the vessel.
energized.
supply.
2.
Ensure that the shore power supply cord is
If the cord is damaged, notify
free from obvious damage.
unit maintenance for repair.
3.
Ensure that the 220 VOLT SUPPLY SWITCH
Place the 220 VOLT SUPPLY
is in the SHORE SUPPLY position.
SWITCH in the SHORE SUPPLY
position.
3. Water heater does not
Check that the circuit breaker for the pump is
Set to ON the circuit breaker.
heat water.
ON.
END OF WORK PACKAGE