Custom Search
 
  
 
TM 55-1925-273-10-1
OPERATOR'S MANUAL
INLAND AND COASTAL LARGE TUG (LT)
THEORY OF OPERATION
FIRE SUPPRESSION SYSTEMS (FM-200, GALLEY GAYLORD, AND PORTABLE)
FM-200 FIRE SUPPRESSION SYSTEM
The engine room and AMS 1 are fitted with a FM-200 fire suppression system. The system is a manually actuated, stand-alone,
total flooding fire suppression system. The system is capable of extinguishing Class A, Class B, and Class C fires when properly
deployed. The system consists of two 600 lb (272 kg) FM-200 cylinder assemblies (figure 1, item 1), a 200 lb (91 kg) FM-200
cylinder assembly (figure 2, item 1), control heads (figures 1 and 2, item 2), discharge nozzles (figures 1 and 2, item 3), and FM-
200 pull boxes (figures 3 and 4).
3
ENGINE ROOM
AMS 1
AMS 2
PORT ENGINE
STBD ENGINE
SEE DETAIL A
2
1
DETAIL A
Figure 1. FM-200 Component Locations (Overhead Systems)
0032 00-1


 