EDG OPERATION
MANUAL RUN
1.
Start EDG (see operating instruction)
2.
Open Main Bus Tie Breaker (Note: For pushbutton operation of motorized Main Bus Tie Breaker, mode
switch must be in "Hand" or "Auto" and door on breaker closed.)
3.
Close EDG breaker.
STAND BY
1.
Place MOED switch to "AUTO".
2.
Place EDG engine control switch to auto start (see operating instructions.)
3.
Ensure that EDG engine is setup for a STAND By operation (see operating instructions.)
4.
Open loss of power from main switchboard:
EDG will start, the main bus tie circuit breaker will open and the EDG breaker will close automatically.
FEEDBACK MODE
With EDG running and breaker closed:
1.  Ensure that no power is fed to the main switchboard (i.e. SSDG1, SSDG 2. and shore power breakers are
open).
2.
Inset key and turn to feedback position.
3.
Close main bus tie breaker and either 1s/E or 2s/E breaker on main switcboard.
Placard 33. Emergency Diesel Generator (Sheet 2 of 2)