TM 55-1925-273-10-1
0069 00
b.
At the main switchboard in the EOS:
(1)
Set the AMMETER switch (figure 13, item 1) to position 1.
(2)
Toggle the speed control switch for GEN 1 GOVERNOR (figure 13, item 2) until the HERTZ (frequency)
meter (figure 15, item 3) reads 60 hertz.
(3)
Turn the BUS GEN. 1 switch (figure 13, item 4) to the 1-2 position.
(4)
Rotate the GENERATOR 1 AUTO. VOLT. RHEO (figure 13, item 5) to read 440 on the A-C VOLTS meter
(figure 13, item 6).
5 4
6
7
3
1
2
8
14
15
9
10
11
13
12
Figure 13. Main Switchboard
c.
At the emergency switchboard in the emergency diesel generator room:
(1)
Set the ENG. CONTROL SW (figure 14, item 1) to the MANUAL position.
(2)
Set the main switchboard bus-tie circuit breaker (figure 14, item 2) to the ON position.
0069 00-9


 