Custom Search
 
  
 
TM 55-1925-273-10-1
0074 00
3.
Commence transferring fuel (filling the day tank):
! CAUTION
Do not operate the fuel oil transfer pumps against a closed fill valve as damage to the pump and/
or piping could occur.
Prior to transferring fuel to the starboard or port day tank, verify that the fuel transfer pump alarm
panel is energized and tested.
NOTE
If filling the day tanks while operating the fuel filter/water separator, use only the selected fuel
oil transfer pump that was lined up in step 1. b. 5 of this procedure. The rated capacity of both
pumps exceeds the rated capacity of the fuel filter/water separator unit.
a.
At the fuel oil transfer pump motor controller(s) 1 and/or 2 (figure 10):
(1)
Set the ON-OFF switch(es) (figure 10, item 1) to ON.
(2)
Verify that the POWER AVAILABLE indicator(s) (figure 10, item 2) energize(s).
ON
1
OFF
2
POWER
AVAILABLE
MOTOR RUN
4
START
3
STOP
5
RESET
Figure 10. Fuel Oil Transfer Pump Motor Controller