Tweet |
Custom Search
|
|
|
||
TM 55-1925-273-10-2
OPERATOR'S MANUAL
INLAND AND COASTAL LARGE TUG (LT)
PREVENTIVE MAINTENANCE CHECKS AND SERVICES INCLUDING LUBRICATION
EMERGENCY DIESEL GENERATOR ROOM
ITEM INTERVAL MAN-
ITEM TO BE
PROCEDURE
EQUIPMENT
NO.
HOUR
CHECKED OR
NOT READY/
SERVICED
AVAILABLE IF:
1
Before
0.1
EMERGENCY
Visually inspect the exterior of the
Any critical controls
SWITCHBOARD
switchboard for damaged or missing
or meters
circuit breakers, meters, controls, and
unserviceable.
lights.
Emergency
Switchboard
BATTERY
NOTE
CHARGER
A high reading indicates the batteries are
weak and are being recharged or that one
or more batteries are unserviceable.
2
Before
0.2
Check battery charger for proper
Charger does not
connections to battery. Ammeter should
operate properly.
read near 0 for trickle charge. If reading
is above 3 AMPS, refer to unit
maintenance.
Battery
Charger
|
||