TM 55-1905-220-14-3
Table 3-42.
Generator - Troubleshooting
NOTE
Most of the generator problems are diagnosed from the switchboard located in the
engine access room. Refer to table 3-43 for switchboard troubleshooting.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
Generator Overheats.
Step 1.
Check the generator covers and cooling fins by observation.
If air passages are dirty - clean.
Step 2.
Check for overloaded.
Refer to table 3-43.
Step 3.
Check for unbalanced load.
Check switchboard and balance generators. Refer to paragraph 2-34.